page_banner

products

YBM(P) 35kV-Class High/Low Voltage Prefabricated Transformer Substation for Wind Power Generation

Short Description:

The Integral Type Transformer for Wind Power Generation is specialized power equipment integrated with the step-up transformer, high-voltage fuse, load switch, low voltage switchgear and relevant auxiliary equipment.


Product Detail

Product Tags

Product Introduction

The Integral Type Transformer for Wind Power Generation is specialized power equipment integrated with the step-up transformer, high-voltage fuse, load switch, low voltage switchgear and relevant auxiliary equipment.

YBM ( P) 35F/0.69kV High/Low Voltage Prefabricated Transformer Substation series products are designed and developed by our company particularly for wind power generation. It boosts the 0.69kV voltage generated by the wind turbines to 35kV and is transmitted to the grid through 35kV cable lines, which makes it an ideal auxiliary equipment for wind power generation systems. Its performances are completely in conformity with standard of GB/T17467 High/Low Voltage Prefabricated Transformer Substation. Developed for purpose of meeting special requirements of wind power generation, the system is a novel prefabricated transformer substation featuring with characteristics like strong nature of complete set, easy installation, short-term construction cycle, low operational expenses, high structural strength and high anti-corrosive properties, etc. It is completely applicable in harsh natural environments like the beach, grassland or desert, etc., with its performances fully satisfying the usage requirements of the wind farms.

Tranformers (82)

Normal Operating Environment Conditions

1.Altitude:≤3000meters;

2.Range of Environment Temperatures:-45℃~+40℃

3.Earthquake Resistance Capacity: horizontal acceleration: lower than 0.4/S2

                           Vertical acceleration: lower than 0.2m/ S2

                               Safety Series:1.67

4.Outdoor speed no higher than:40m/s

5.Location for installation: no violent vibration, gradient no bigger than 3°

6.Service Location: should not contain conductive dust or corrosive, flammable and explosive hazardous objects which may be harmful to metals and insulating materals;

In occasions where the aforesaid normal operating environmental conditions have been exceeded, the user may consult with the company for a resolution.

Main Technical Parameters

Rated Parameters for Box-type Substation

1.1 Voltage
System Voltage: 35kV (36.75kV,38.5kV)
Maximum Operating Voltage on the High-side: 40.5kV
Rated Voltage on the Low-side: 0.69kV

1.2 Rated Frequency: 50Hz

1.3 Rated Insulation Level (adjustable according to altitude) 
Power-frequency Withstand Voltage of the High-side of Transformer: 95kV (active part 85kV)
Withstand Voltage of the Impulse Peak: 200kV
Power-frequency Withstand Voltage of the Low-side of Transformer: 5kV

1.4 Phase Number: Three Phases

1.5 Box Protection Class: high-low voltage chamber IP54, after opening the door of high voltage chamber IP3X

Main Technical Parameters of Transformer

2.1 Technical Standards

The transformer is in conformity with GB1094.1—1094.5 Power Transformer and GB6451.1 Specification and Technical Requirements for Three-phase Oil-immersed Power Transformers

Technical Parameters

Tranformers (83)

  • Previous:
  • Next:

  • Write your message here and send it to us